############################################################### acstat System ac1.matrix.msu.edu is ok, 70 degF, 17% humidity Active: Power Cooling Capacity in use: Cooling 100%, Heating 0% Run time (hours): Compressor 35876, Fan 27534, Humidifier 0, Reheat1 0, Reheat2 0, Reheat3 0 System ac2.matrix.msu.edu is ok, 71 degF, 16% humidity Active: Power Capacity in use: Cooling 0%, Heating 0% Run time (hours): Compressor 15607, Fan 25317, Humidifier 0, Reheat1 0, Reheat2 0, Reheat3 0 System ac3.matrix.msu.edu is ok, 68 degF, 18% humidity Active: Power Cooling Capacity in use: Cooling 100%, Heating 0% Run time (hours): Compressor 39212, Fan 27454, Humidifier 0, Reheat1 0, Reheat2 0, Reheat3 0 ############################################################### ups output status PowerNet-MIB::upsBasicOutputStatus.0 = INTEGER: onLine(2) ############################################################### ups last self test PowerNet-MIB::upsAdvTestLastDiagnosticsDate.0 = STRING: "09/02/2024" ############################################################### ups reason for last transfer PowerNet-MIB::upsAdvInputLineFailCause.0 = INTEGER: selfTest(9) ############################################################### ups external temp sensor degrees C PowerNet-MIB::iemStatusProbeCurrentTemp.1 = INTEGER: 24 ############################################################### ups battery capacity % PowerNet-MIB::upsAdvBatteryCapacity.0 = Gauge32: 100 ############################################################### ups remaining runtime PowerNet-MIB::upsAdvBatteryRunTimeRemaining.0 = Timeticks: (192000) 0:32:00.00 ############################################################### ups output current (amps) PowerNet-MIB::upsAdvOutputLoad.0 = Gauge32: 21 ############################################################### ups battery bus voltage PowerNet-MIB::upsAdvBatteryActualVoltage.0 = INTEGER: 138 ############################################################### ups battery bus current (amps) PowerNet-MIB::upsAdvBatteryCurrent.0 = INTEGER: 0 ############################################################### ups battery abnormal conditions PowerNet-MIB::upsAdvStateAbnormalConditions.0 = STRING: "00000000000000000000000000000000" An ASCII string containing the 32 flags representing the current active UPS faults. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If this variable is not supported by the connected UPS, this variable is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 32, and read from left to right. The flags are defined as follows: Flag 1: Power Module Failure Flag 2: Main Intelligence Module Failure Flag 3: Redundant Intelligence Module Failure Flag 4: Battery Failure Flag 5: Load(kVA) Alarm Threshold Violation Flag 6: Redundancy Lost Flag 7: Redundancy Below Alarm Threshold Flag 8: Bypass not in Range; Either Frequency or Voltage Flag 9: Bypass Contactor Stuck in Bypass Condition Flag 10: Bypass Contactor Stuck in On-Line Condition Flag 11: In Bypass due to an Internal Fault Flag 12: In Bypass due to an Overload Flag 13: In Maintenance Bypass Flag 14: Input Circuit Braker Tripped Open Flag 15: System Level Fan Failure Flag 16: Redundant Intelligent Module in Control Flag 17: IIC Inter-Module Communication Failure Flag 18: No Working Power Modules Flag 19: Load Shutdown From Bypass; Input Frequency Flag 20: Runtime Below Alarm Threshold Flag 21: Extended Run Frame Fault Flag 22: Output Voltage out of Range Flag 23: UPS Not Synchronized Flag 24: No Batteries Installed Flag 25: Battery Voltage High Flag 26: UPS Specific Fault Detected Flag 27: Site Wiring Fault Flag 28: Backfeed Protection Relay Opened Flag 29: Flag 30: Flag 31: Flag 32: ############################################################### ups external temp sensor degrees C PowerNet-MIB::iemStatusProbeCurrentTemp.1 = INTEGER: 24 ############################################################### ups battery capacity % PowerNet-MIB::upsAdvBatteryCapacity.0 = Gauge32: 100 ############################################################### ups remaining runtime PowerNet-MIB::upsAdvBatteryRunTimeRemaining.0 = Timeticks: (192000) 0:32:00.00 ############################################################### ups output current (amps) PowerNet-MIB::upsAdvOutputLoad.0 = Gauge32: 21 ############################################################### ups battery bus voltage PowerNet-MIB::upsHighPrecBatteryActualVoltage.0 = INTEGER: 1383 ############################################################### ups battery bus current (amps) PowerNet-MIB::upsAdvBatteryCurrent.0 = INTEGER: 0 ############################################################### ups battery abnormal conditions PowerNet-MIB::upsAdvStateAbnormalConditions.0 = STRING: "00000000000000000000000000000000" An ASCII string containing the 32 flags representing the current active UPS faults. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If this variable is not supported by the connected UPS, this variable is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 32, and read from left to right. The flags are defined as follows: Flag 1: Power Module Failure Flag 2: Main Intelligence Module Failure Flag 3: Redundant Intelligence Module Failure Flag 4: Battery Failure Flag 5: Load(kVA) Alarm Threshold Violation Flag 6: Redundancy Lost Flag 7: Redundancy Below Alarm Threshold Flag 8: Bypass not in Range; Either Frequency or Voltage Flag 9: Bypass Contactor Stuck in Bypass Condition Flag 10: Bypass Contactor Stuck in On-Line Condition Flag 11: In Bypass due to an Internal Fault Flag 12: In Bypass due to an Overload Flag 13: In Maintenance Bypass Flag 14: Input Circuit Braker Tripped Open Flag 15: System Level Fan Failure Flag 16: Redundant Intelligent Module in Control Flag 17: IIC Inter-Module Communication Failure Flag 18: No Working Power Modules Flag 19: Load Shutdown From Bypass; Input Frequency Flag 20: Runtime Below Alarm Threshold Flag 21: Extended Run Frame Fault Flag 22: Output Voltage out of Range Flag 23: UPS Not Synchronized Flag 24: No Batteries Installed Flag 25: Battery Voltage High Flag 26: UPS Specific Fault Detected Flag 27: Site Wiring Fault Flag 28: Backfeed Protection Relay Opened Flag 29: Flag 30: Flag 31: Flag 32: